Electrical Datum
One datum per point. No site guessing.
v1.4 · 14 Nov 2026
Window and door heights have their own sheet: Doors & windows height + coordinate guide
The water points sheet: Water inlets and outlets · Joinery datum
ELS planning references
This sheet provides ELS planning references. Final locations and electrical arrangements must meet applicable Sarawak requirements and the selected equipment’s installation instructions, verified by the appointed electrical installation contractor.
This sheet does not establish statutory compliance, and a datum schedule alone is not an electrical design or an approval.
Electrical verification stays with the appropriately registered contractor. ELS+ delivery applies only to contracted works.
The nine starting coordination datums
Every point on the schedule except the floor box and the island socket starts from one of these nine heights, in millimetres. They are starting points for coordination, not final installation positions: the final position follows the room's geometry, the equipment's instructions, access and the applicable requirements.
- 350General
- 600Low appliance / outdoor
- 700Bedside
- 950TV
- 1100Desk
- 1150Kitchen worktop
- 1200Service / fridge / vanity
- 1400Controls / isolators
- 2200Hood / AC / high-level equipment
The schedule by use
Heights in millimetres, FFL → CL.
The worktop- and TV-related points follow the worktop height and screen position confirmed in the room's Fit Check, so they move with them.
Each row shows the starting datum, what can change it, and the position a project confirms. The project-confirmed position is set on the project's M&E plan, so it is blank here. Every status on this page is a label only: this page records no approval.
| Point | ID | Starting datum (mm) | Placement rule | Can change it | Confirmed · status |
|---|---|---|---|---|---|
| General 13A socket | GEN-01 | 350 | Dry-area universal socket | As the group's line | — · Proposed |
| Bedside socket / USB | BED-01 | 700 | Above typical bedside cabinet | Actual bedside furniture, mattress height and cable access. A reference height, not a guaranteed concealed or reachable position. | — · Proposed |
| TV console socket | LIV-01 | 350 | Low equipment zone | As the group's line | — · Proposed |
| Wall-TV power + data | LIV-02 | 950 | Concealed behind TV | The screen bracket, screen size, drawers and cable access. A reference height, not a guaranteed concealed position. | — · Proposed |
| Desk / study socket | GEN-02 | 1100 | Above typical 750 mm desk | The actual desk, its drawers and cable access (the reference assumes a typical 750 mm desk). Where the desk sits under a window, set the socket position together with the window's frame-bottom height (see the doors and windows height and coordinate guide). | — · Proposed |
| Router / network equipment power | LIV-03 | 1100 | Prefer dedicated structured-media location | As the group's line | — · Proposed |
What can change a row: Actual furniture, screen and bracket, drawers and cable access. A reference height, not a guaranteed concealed or reachable position.
General living is not a room. These are shared starting points that the room schedules use.
| Point | ID | Starting datum (mm) | Placement rule | Can change it | Confirmed · status |
|---|---|---|---|---|---|
| Kitchen countertop socket | KIT-01 | 1150 | Typical 900 mm worktop | Show the actual worktop height beside the socket position (1150 mm assumes a typical 900 mm worktop). Check plate clearance, backsplash joints, appliances and splash exposure. Where a window sits above the worktop, set the socket position together with the window's frame-bottom height (see the doors and windows height and coordinate guide). | — · Proposed |
| Kitchen island socket | KIT-02 | No fixed height | set per island, below the worktop on a side or end panel, coordinated with the island's height, water exposure and the chosen accessory | The island's height, water exposure, access and the chosen accessory. No universal height is substituted. | — · Proposed |
| Refrigerator dedicated socket | KIT-03 | 1200 | Adjacent accessible service zone, not trapped behind fridge | As the group's line | — · Proposed |
| Dishwasher socket | KIT-04 | 600 | In adjacent cabinet/service bay, never directly behind dishwasher | As the group's line | — · Proposed |
| Under-counter oven connection / socket | KIT-05 | 600 | Adjacent cabinet/service bay | As the group's line | — · Proposed |
| Built-in oven isolator | KIT-06 | 1400 | Accessible outside appliance cavity | Reach, doors, furniture and safe operation; an accessible project-specific position is allowed. | — · Proposed |
| Built-in microwave socket | KIT-07 | 1400 | Adjacent service cabinet | Reach, doors, furniture and safe operation; an accessible project-specific position is allowed. | — · Proposed |
| Coffee-machine / appliance tower socket | KIT-08 | 1400 | Accessible within adjacent appliance/service zone | Reach, doors, furniture and safe operation; an accessible project-specific position is allowed. | — · Proposed |
| Cooker / induction hob isolator | KIT-09 | 1400 | Dedicated circuit; not directly above hob | Reach, doors, furniture and safe operation; an accessible project-specific position is allowed. | — · Proposed |
| Cooker hood socket | KIT-10 | 2200 | Concealed/accessibly located above or within hood cabinet | As the group's line | — · Proposed |
What can change a row: The actual worktop height, backsplash joints, appliances, plate clearance and splash exposure.
| Point | ID | Starting datum (mm) | Placement rule | Can change it | Confirmed · status |
|---|---|---|---|---|---|
| Washing-machine socket | UTL-01 | 1200 | Beside machine, away from hoses | As the group's line | — · Proposed |
| Dryer socket | UTL-02 | 1200 | Dedicated accessible point | As the group's line | — · Proposed |
What can change a row: The machine's own instructions, hose positions and service access.
| Point | ID | Starting datum (mm) | Placement rule | Can change it | Confirmed · status |
|---|---|---|---|---|---|
| Mirror / mirror-cabinet power | BAT-01 | 1200 | Coordinate basin/mirror geometry | As the group's line | — · Proposed |
| Bathroom shaver socket | BAT-02 | 1200 | Only where wet-zone requirements permit | As the group's line | — · Proposed |
| Instant water-heater isolator | BAT-03 | 1400 | Outside inappropriate wet zone | Reach, doors, furniture and safe operation; an accessible project-specific position is allowed. | — · Proposed |
| Storage water-heater isolator | BAT-04 | 1400 | Accessible outside wet zone | Reach, doors, furniture and safe operation; an accessible project-specific position is allowed. | — · Proposed |
What can change a row: Wet-area review first, then basin and shower positions, mirror cabinet and the equipment's instructions. Height never implies permission.
| Point | ID | Starting datum (mm) | Placement rule | Can change it | Confirmed · status |
|---|---|---|---|---|---|
| Air-conditioner isolator | GEN-03 | 2200 | Near equipment, accessible for servicing | As the group's line | — · Proposed |
| 15A dedicated AC/equipment outlet | GEN-04 | 2200 | Where equipment/system specifically requires 15A | As the group's line | — · Proposed |
| Water-pump isolator | UTL-03 | 1200 | Accessible, dry/serviceable location | As the group's line | — · Proposed |
What can change a row: The equipment's own instructions, its mounting position and service access.
| Point | ID | Starting datum (mm) | Placement rule | Can change it | Confirmed · status |
|---|---|---|---|---|---|
| Outdoor general socket | UTL-04 | 600 | Weatherproof and above normal splash zone | As the group's line | — · Proposed |
| Balcony socket | UTL-05 | 600 | Weatherproof | As the group's line | — · Proposed |
| Autogate power / isolator | UTL-06 | 1200 | Protected service location | As the group's line | — · Proposed |
| CCTV / security equipment power | UTL-07 | 2200 | High-level service point where appropriate | As the group's line | — · Proposed |
What can change a row: Site-specific rain, splash and flood exposure. Height alone does not establish suitability.
| Point | ID | Starting datum (mm) | Placement rule | Can change it | Confirmed · status |
|---|---|---|---|---|---|
| Floor box | GEN-05 | 0 · flush with FFL | Flush with finished floor; location dimensioned in plan | As the group's line | — · Proposed |
What can change a row: The plan dimensions and the finished floor build-up.
| Point | ID | Starting datum (mm) | Placement rule | Can change it | Confirmed · status |
|---|---|---|---|---|---|
| Light switch | GEN-06 | 1400 | ELS control datum | As the group's line | — · Proposed |
| General appliance isolator | GEN-07 | 1400 | ELS common control datum | As the group's line | — · Proposed |
What can change a row: Reach, doors, furniture and safe operation; an accessible project-specific position is allowed.
The points of each space, for four ELS reference homes, are listed on one page with the water points beside them: Points by space
Verification status
- Proposed
- Coordinated
- Contractor verified
- Installed and tested
A project's own records move a point along this sequence. On this public sheet the statuses are labels only, and nothing here is approved.
Optional kitchen interfaces
Project-specific, with no reference height. Each appears on a project only when it is selected, and none is priced or included automatically.
- KIT-P1 Water purifierA power point beside the under-sink or tower position, the water connection and access to change the filter.
- KIT-P2 Waste disposerA switched power point, the sink and drain position, and access to service it.
- KIT-P3 Cabinet and task-lighting driversThe driver position, the switching, and access to replace a driver without removing fixed cabinetry.
- KIT-P4 Future dishwasher provisionA power and water provision in the adjacent service bay, never directly behind the dishwasher, with the actual installation instructions followed.
- KIT-P5 Appliance garageSocket positions inside the garage and the cable route, kept clear of heat, steam and moving doors.
- KIT-P6 Powered cabinet accessoriesThe power and control position for each motorised or powered accessory, and access to service it.
- KIT-P7 Kitchen coolingThe connection and isolation for any fan or air-conditioning unit serving the kitchen, with its service access.
- KIT-P8 Island power routingHow power reaches the island through the floor or the cabinetry, coordinated with the island's height, water exposure and the chosen accessory.
Other project-specific points
Project-specific, with no reference height. Each appears on a project only when it is selected, and none is priced or included automatically.
- GEN-P1 Doorbell push-button or video doorbell / intercom entrance stationThe door and its frame, the entrance wall and the cable route to the indoor unit.
- GEN-P2 Private distribution boardService access to the board, the meter position and the wall or cabinet it sits in.
- GEN-P3 Wired Wi-Fi access pointThe ceiling or wall position and the data cable route to it.
- GEN-P4 CCTV recorderVentilation around the recorder and the cable routes to the cameras and the network.
- GEN-P5 DimmerThe lamp and driver it controls, and the switch position.
Four rooms, five checks
Kitchen, bedroom, living room and bathroom each get the same five checks, with the points grouped by everyday use. Optional equipment appears only when you select it, and nothing here is an automatic inclusion. A height beside an item is its point's starting coordination datum, in millimetres; an item with no height is project-specific.
- Position Dimension the point horizontally on the plan and vertically from finished floor level.
- Fit Check the actual furniture, accessory plate, appliance and cabinet dimensions.
- Use Confirm reach, switching, glare, trailing cables and simultaneous appliance use.
- Service Show how connections, drivers and equipment can be isolated, accessed and replaced.
- Verification Distinguish proposed design positions from contractor-verified electrical arrangements.
Kitchen
Coordinate with: Actual appliances, worktop height, backsplash, sink and plumbing, cabinet modules, ventilation and service access.
Appliances, simultaneous use and cabinet services are coordinated together.
- Position
- Dimension each point on the plan and from FFL against the actual worktop height and backsplash joints; the island's point is set per island.
- Fit
- Check the actual appliance, worktop, backsplash, sink and cabinet-module dimensions, so that no plate or connection sits behind fixed furniture or under equipment.
- Use
- Confirm reach at the worktop, which appliances run together, and where cables would trail across the work zone.
- Service
- Show how each appliance, driver and cooling connection is isolated, reached and replaced without removing fixed cabinetry; keep ventilation and service access clear.
- Verification
- Mark each point Proposed until the appointed electrical installation contractor has verified the arrangement. Appliance connections follow the selected model's installation instructions.
Cooking
- KIT-09 1400 mm
- KIT-05 600 mm · KIT-06 1400 mm
- KIT-07 1400 mm
- KIT-10 2200 mm
Cold, wet and cleaning
- KIT-03 1200 mm
- KIT-04 600 mm
- Project-specific: to be coordinated
- Project-specific: to be coordinated
- Project-specific: to be coordinated
Worktop and island
- KIT-01 1150 mm
- KIT-02 no fixed height, set per island
- KIT-08 1400 mm
- Project-specific: to be coordinated
- Project-specific: to be coordinated
- Project-specific: to be coordinated
Light and air
- Project-specific: to be coordinated
- Project-specific: to be coordinated
Bedroom
Coordinate with: Bed and mattress height, bedside furniture, wardrobe doors, mirrors, curtain pockets, airflow and sleeping positions.
Both sides of the bed are covered, and so is switching from the entry and from the bed.
- Position
- Dimension both bedsides, the entry and bedside switching, and each light on the plan and from FFL, against the bed and mattress height.
- Fit
- Check the bed, mattress, bedside furniture, wardrobe doors, mirrors and curtain pockets, so that no plate or switch is covered or struck by a door.
- Use
- Confirm reach from each side of the bed, switching from the entry and from the bed, glare at the sleeping positions and trailing charging cables.
- Service
- Show how drivers, air-conditioning and fan isolation and any curtain motor are reached and replaced, with airflow kept clear.
- Verification
- Mark each point Proposed until the appointed electrical installation contractor has verified the arrangement. Air-conditioning, fan and curtain-motor arrangements are the contractor's to verify.
Beside the bed
- BED-01 700 mm
- BED-01 700 mm
Light
- GEN-06 1400 mm
- GEN-06 1400 mm
- Project-specific: to be coordinated
- Project-specific: to be coordinated
Dressing and desk
- Project-specific: to be coordinated
- GEN-02 1100 mm · LIV-02 950 mm
Air and curtains
- GEN-03 2200 mm
- Project-specific: to be coordinated
- Project-specific: to be coordinated
Living room
Coordinate with: Final furniture layout, TV bracket and screen, console, cable routes, ceiling details, glare and maintenance access.
TV, seating, media and data, and layered lighting are coordinated together.
- Position
- Dimension the TV, media and data points, seating-area charging, lamp sockets and each lighting layer on the plan and from FFL, against the final furniture layout.
- Fit
- Check the TV bracket and screen, console, seating, cable routes and ceiling details, so that no plate or connection is hidden behind fixed furniture.
- Use
- Confirm reach from the seating, glare on the screen, trailing cables across walkways, and which media and work equipment run together.
- Service
- Show how the router, media equipment, drivers and air-conditioning isolation are reached and replaced, and how lamps and fittings are maintained.
- Verification
- Mark each point Proposed until the appointed electrical installation contractor has verified the arrangement. Network, media and lighting arrangements are verified alongside the power.
Screen and media
- LIV-01 350 mm · LIV-02 950 mm
- LIV-03 1100 mm
Seating and work
- Project-specific: to be coordinated
- GEN-01 350 mm
- GEN-02 1100 mm
Light
- Project-specific: to be coordinated
Air and curtains
- GEN-03 2200 mm
- Project-specific: to be coordinated
- Project-specific: to be coordinated
Bathroom
Coordinate with: Wet-area restrictions, basin and shower positions, mirror cabinet, ceiling, plumbing, equipment instructions and access.
Wet-area review before any point is confirmed. No height on this sheet implies permission to install an accessory there.
- Position
- Do the wet-area review first. Only then dimension any point on the plan and from FFL; a height never implies a point may go there.
- Fit
- Check the basin and shower positions, mirror cabinet, ceiling, plumbing and the equipment's own dimensions and instructions.
- Use
- Confirm reach and switching, and what is used together, such as the mirror light, a demister and the exhaust fan.
- Service
- Show how the water heater, exhaust fan and mirror equipment can be isolated, reached and replaced.
- Verification
- Wet-area suitability, equipment selection and electrical protection need the appointed electrical contractor’s verification before any point is confirmed.
At the mirror
- BAT-01 1200 mm
- Project-specific: to be coordinated
- BAT-02 1200 mm
Water and air
- BAT-03 1400 mm · BAT-04 1400 mm
- Project-specific: to be coordinated
- Project-specific: to be coordinated
Light
- Project-specific: to be coordinated
Connection schedule, a specimen
Height answers only one part of electrical planning. A connection schedule records, for each appliance or point, what it needs and who verifies it. These three lines are illustrations: they describe no project and no product, and ELS calculates no cable size, protection or circuit rating.
KIT-05
- Point ID
- KIT-05
- Room
- Kitchen
- Appliance and model status
- Under-counter oven; model not chosen yet
- Rated load
- From the selected product's documentation
- Connection requirement
- Per the manufacturer's instructions; the contractor confirms the arrangement
- Plan position
- Wall and offset dimensioned on the plan
- Final height, FFL to CL
- Set per project; the reference datum is 600 mm
- Isolation and access
- Adjacent service bay, reachable without removing the oven
- Cabinet, plumbing and lighting interfaces
- Cabinet cut-out and ventilation
- Trade
- Appointed electrical installation contractor
- Verification status
- Proposed
KIT-02
- Point ID
- KIT-02
- Room
- Kitchen
- Appliance and model status
- Island socket; accessory not chosen yet
- Rated load
- From the selected product's documentation
- Connection requirement
- Per the manufacturer's instructions; the contractor confirms the arrangement
- Plan position
- Wall and offset dimensioned on the plan
- Final height, FFL to CL
- Set per island, below the worktop on a side or end panel
- Isolation and access
- Reachable without moving fixed furniture
- Cabinet, plumbing and lighting interfaces
- Island panel, floor or cabinet routing, water exposure
- Trade
- Appointed electrical installation contractor
- Verification status
- Proposed
BAT-03
- Point ID
- BAT-03
- Room
- Bathroom
- Appliance and model status
- Water heater; model not chosen yet
- Rated load
- From the selected product's documentation
- Connection requirement
- Per the manufacturer's instructions; the contractor confirms the arrangement
- Plan position
- Wall and offset dimensioned on the plan
- Final height, FFL to CL
- Set after the wet-area review; the reference datum is 1400 mm
- Isolation and access
- Isolation outside the wet area where the contractor requires it
- Cabinet, plumbing and lighting interfaces
- Plumbing and the ceiling or wall
- Trade
- Appointed electrical installation contractor
- Verification status
- Proposed
Appliance load schedule
Tell us which appliances you use together, so their power requirements and positions can be coordinated before work starts.
This page stays focused on where each point goes. The load schedule records what each point must serve, and is linked to it by point ID. It uses your own equipment list, where you type the model and the quantity.
- Manufacturer-rated current takes precedence over an estimate.
- An unknown value stays unknown. It is never shown as zero.
- Rated input power only: cooling capacity and cooking output are not electrical input.
- The voltage is the appliance's rated voltage, or unknown. ELS assumes none.
- Estimated current is input watts ÷ voltage, for a single-phase load, assuming power factor 1. Motors, compressors and electronic equipment can need more information from the manufacturer.
- A sum of currents is a connected-load estimate. It is not the home's maximum demand.
- Appliance current, plug or fuse rating and circuit-breaker rating are different things. ELS sizes no cable, breaker, protection or circuit, and a low estimate does not show that a socket is suitable.
- For lighting, record the driver's electrical input and the load it supports, and where the driver can be reached to replace it. Low-voltage LED output current is not mains input current.
- Your inputs and the contractor's verification are kept apart. This page cannot mark anything contractor verified.
What to capture in each room
- Kitchen
- Hob, oven, microwave, kettle, coffee machine, dishwasher, fridge, hood, purifier, an optional disposer and countertop appliances.
- Bedroom
- Air-conditioning, fan, dressing appliances such as a hair dryer, desk equipment, TV, lighting and powered curtains.
- Living room
- Air-conditioning, fan, TV and media, computer or work corner, lighting, charging, and powered furniture or curtains.
- Bathroom
- Instant or storage water heater, ventilation, mirror demister, permitted grooming equipment and an optional powered toilet.
Specimen lines
KIT-C09 ← KIT-08
- Point ID
- KIT-C09
- Appliance
- Illustration only: a hypothetical appliance
- Model and quantity
- No model; quantity 1
- Input power
- 2,300 W
- Voltage
- 230 V
- Phase
- Single phase
- Rated current
- unknown
- Estimated current
- 10.0 A (2,300 W ÷ 230 V; single phase, power factor 1 assumed)
- Source or reference
- The paper's own illustration, not a product
- Connection requirement
- Per the manufacturer's instructions; the contractor confirms
- Simultaneous-use group
- A
- Verification status
- Proposed
KIT-C03 ← KIT-03
- Point ID
- KIT-C03
- Appliance
- Fridge; model not chosen yet
- Model and quantity
- No model; quantity 1
- Input power
- unknown
- Voltage
- unknown
- Phase
- unknown
- Rated current
- unknown
- Estimated current
- unknown
- Source or reference
- From the selected product's nameplate or manual
- Connection requirement
- Per the manufacturer's instructions; the contractor confirms
- Simultaneous-use group
- B
- Verification status
- Proposed
Connected-load estimate (specimen): 10.0 A at 230 V (1 row). The second line has no current and no voltage, so it is not added and is not counted as zero.
Appliance & Equipment Coordination
Your appliance load schedule
Kept on this device, with your equipment list. Nothing is sent to ELS, ALUMAX or anyone else; you copy, print or download what you choose to send. Your inputs are yours: this page cannot mark anything verified by an electrical contractor.
How to use it
- An ELS design standard, not a statutory height. This sheet provides ELS planning references. Final locations and electrical arrangements must meet applicable Sarawak requirements and the selected equipment’s installation instructions, verified by the appointed electrical installation contractor.
- The appliance manual wins. Check dishwasher, oven, fridge, AC, water heater and cooker connection positions at design freeze.
- Wet zones win. Bathroom points go only where the wet-zone requirements permit.
- Plan position is drawn, height is this sheet. Mark the wall and offset on the M&E plan; the height comes from the schedule.
- Wiring is done by a registered electrical contractor.
Not on this sheet?
A point this schedule does not list (for example an EV charger) is set per project and drawn on the M&E plan until ELS adds a datum for it.
Measured FFL → CL
Every height is measured from finished floor level (FFL) to the centre line (CL) of the accessory — not the underside of the box, not the top of the plate. Set FFL from the finished floor build-up, not the slab.
The floor box is the one exception: it sits flush with FFL, and its position is dimensioned on the plan.