ELS Design Standard · Residential

Electrical Datum

One datum per point. No site guessing.

v1.4 · 14 Nov 2026

Window and door heights have their own sheet: Doors & windows height + coordinate guide

The water points sheet: Water inlets and outlets · Joinery datum

ELS planning references

This sheet provides ELS planning references. Final locations and electrical arrangements must meet applicable Sarawak requirements and the selected equipment’s installation instructions, verified by the appointed electrical installation contractor.

This sheet does not establish statutory compliance, and a datum schedule alone is not an electrical design or an approval.

Electrical verification stays with the appropriately registered contractor. ELS+ delivery applies only to contracted works.

The nine starting coordination datums

Every point on the schedule except the floor box and the island socket starts from one of these nine heights, in millimetres. They are starting points for coordination, not final installation positions: the final position follows the room's geometry, the equipment's instructions, access and the applicable requirements.

  1. 350General
  2. 600Low appliance / outdoor
  3. 700Bedside
  4. 950TV
  5. 1100Desk
  6. 1150Kitchen worktop
  7. 1200Service / fridge / vanity
  8. 1400Controls / isolators
  9. 2200Hood / AC / high-level equipment
030060090012001500180021002400Desk 750Worktop 900Wall cabinet 1500350General600Low appliance / outdoor700Bedside950TV1100Desk1150Kitchen worktop1200Service / fridge / vanity1400Controls / isolators2200Hood / AC / high-level equipmentFFL 0
Wall elevation drawn to scale, 0 to 2,400 mm. Each square is an illustrative 86 × 86 mm plate: actual sockets, isolators and fittings vary. The dashed desk, worktop and wall-cabinet lines are illustrative furniture reference heights, not datums; the actual fitting dimensions, furniture and room geometry govern.

The schedule by use

Heights in millimetres, FFL → CL.

The worktop- and TV-related points follow the worktop height and screen position confirmed in the room's Fit Check, so they move with them.

Each row shows the starting datum, what can change it, and the position a project confirms. The project-confirmed position is set on the project's M&E plan, so it is blank here. Every status on this page is a label only: this page records no approval.

General living 6
PointIDStarting datum (mm)Placement ruleCan change itConfirmed · status
General 13A socketGEN-01350Dry-area universal socketAs the group's line— · Proposed
Bedside socket / USBBED-01700Above typical bedside cabinetActual bedside furniture, mattress height and cable access. A reference height, not a guaranteed concealed or reachable position.— · Proposed
TV console socketLIV-01350Low equipment zoneAs the group's line— · Proposed
Wall-TV power + dataLIV-02950Concealed behind TVThe screen bracket, screen size, drawers and cable access. A reference height, not a guaranteed concealed position.— · Proposed
Desk / study socketGEN-021100Above typical 750 mm deskThe actual desk, its drawers and cable access (the reference assumes a typical 750 mm desk). Where the desk sits under a window, set the socket position together with the window's frame-bottom height (see the doors and windows height and coordinate guide).— · Proposed
Router / network equipment powerLIV-031100Prefer dedicated structured-media locationAs the group's line— · Proposed

What can change a row: Actual furniture, screen and bracket, drawers and cable access. A reference height, not a guaranteed concealed or reachable position.

General living is not a room. These are shared starting points that the room schedules use.

Kitchen 10
PointIDStarting datum (mm)Placement ruleCan change itConfirmed · status
Kitchen countertop socketKIT-011150Typical 900 mm worktopShow the actual worktop height beside the socket position (1150 mm assumes a typical 900 mm worktop). Check plate clearance, backsplash joints, appliances and splash exposure. Where a window sits above the worktop, set the socket position together with the window's frame-bottom height (see the doors and windows height and coordinate guide).— · Proposed
Kitchen island socketKIT-02No fixed heightset per island, below the worktop on a side or end panel, coordinated with the island's height, water exposure and the chosen accessoryThe island's height, water exposure, access and the chosen accessory. No universal height is substituted.— · Proposed
Refrigerator dedicated socketKIT-031200Adjacent accessible service zone, not trapped behind fridgeAs the group's line— · Proposed
Dishwasher socketKIT-04600In adjacent cabinet/service bay, never directly behind dishwasherAs the group's line— · Proposed
Under-counter oven connection / socketKIT-05600Adjacent cabinet/service bayAs the group's line— · Proposed
Built-in oven isolatorKIT-061400Accessible outside appliance cavityReach, doors, furniture and safe operation; an accessible project-specific position is allowed.— · Proposed
Built-in microwave socketKIT-071400Adjacent service cabinetReach, doors, furniture and safe operation; an accessible project-specific position is allowed.— · Proposed
Coffee-machine / appliance tower socketKIT-081400Accessible within adjacent appliance/service zoneReach, doors, furniture and safe operation; an accessible project-specific position is allowed.— · Proposed
Cooker / induction hob isolatorKIT-091400Dedicated circuit; not directly above hobReach, doors, furniture and safe operation; an accessible project-specific position is allowed.— · Proposed
Cooker hood socketKIT-102200Concealed/accessibly located above or within hood cabinetAs the group's line— · Proposed

What can change a row: The actual worktop height, backsplash joints, appliances, plate clearance and splash exposure.

Laundry 2
PointIDStarting datum (mm)Placement ruleCan change itConfirmed · status
Washing-machine socketUTL-011200Beside machine, away from hosesAs the group's line— · Proposed
Dryer socketUTL-021200Dedicated accessible pointAs the group's line— · Proposed

What can change a row: The machine's own instructions, hose positions and service access.

Bathroom 4
PointIDStarting datum (mm)Placement ruleCan change itConfirmed · status
Mirror / mirror-cabinet powerBAT-011200Coordinate basin/mirror geometryAs the group's line— · Proposed
Bathroom shaver socketBAT-021200Only where wet-zone requirements permitAs the group's line— · Proposed
Instant water-heater isolatorBAT-031400Outside inappropriate wet zoneReach, doors, furniture and safe operation; an accessible project-specific position is allowed.— · Proposed
Storage water-heater isolatorBAT-041400Accessible outside wet zoneReach, doors, furniture and safe operation; an accessible project-specific position is allowed.— · Proposed

What can change a row: Wet-area review first, then basin and shower positions, mirror cabinet and the equipment's instructions. Height never implies permission.

Mechanical 3
PointIDStarting datum (mm)Placement ruleCan change itConfirmed · status
Air-conditioner isolatorGEN-032200Near equipment, accessible for servicingAs the group's line— · Proposed
15A dedicated AC/equipment outletGEN-042200Where equipment/system specifically requires 15AAs the group's line— · Proposed
Water-pump isolatorUTL-031200Accessible, dry/serviceable locationAs the group's line— · Proposed

What can change a row: The equipment's own instructions, its mounting position and service access.

External 4
PointIDStarting datum (mm)Placement ruleCan change itConfirmed · status
Outdoor general socketUTL-04600Weatherproof and above normal splash zoneAs the group's line— · Proposed
Balcony socketUTL-05600WeatherproofAs the group's line— · Proposed
Autogate power / isolatorUTL-061200Protected service locationAs the group's line— · Proposed
CCTV / security equipment powerUTL-072200High-level service point where appropriateAs the group's line— · Proposed

What can change a row: Site-specific rain, splash and flood exposure. Height alone does not establish suitability.

Special 1
PointIDStarting datum (mm)Placement ruleCan change itConfirmed · status
Floor boxGEN-050 · flush with FFLFlush with finished floor; location dimensioned in planAs the group's line— · Proposed

What can change a row: The plan dimensions and the finished floor build-up.

Controls 2
PointIDStarting datum (mm)Placement ruleCan change itConfirmed · status
Light switchGEN-061400ELS control datumAs the group's line— · Proposed
General appliance isolatorGEN-071400ELS common control datumAs the group's line— · Proposed

What can change a row: Reach, doors, furniture and safe operation; an accessible project-specific position is allowed.

The points of each space, for four ELS reference homes, are listed on one page with the water points beside them: Points by space

Verification status

  1. Proposed
  2. Coordinated
  3. Contractor verified
  4. Installed and tested

A project's own records move a point along this sequence. On this public sheet the statuses are labels only, and nothing here is approved.

Optional kitchen interfaces

Project-specific, with no reference height. Each appears on a project only when it is selected, and none is priced or included automatically.

  • KIT-P1 Water purifierA power point beside the under-sink or tower position, the water connection and access to change the filter.
  • KIT-P2 Waste disposerA switched power point, the sink and drain position, and access to service it.
  • KIT-P3 Cabinet and task-lighting driversThe driver position, the switching, and access to replace a driver without removing fixed cabinetry.
  • KIT-P4 Future dishwasher provisionA power and water provision in the adjacent service bay, never directly behind the dishwasher, with the actual installation instructions followed.
  • KIT-P5 Appliance garageSocket positions inside the garage and the cable route, kept clear of heat, steam and moving doors.
  • KIT-P6 Powered cabinet accessoriesThe power and control position for each motorised or powered accessory, and access to service it.
  • KIT-P7 Kitchen coolingThe connection and isolation for any fan or air-conditioning unit serving the kitchen, with its service access.
  • KIT-P8 Island power routingHow power reaches the island through the floor or the cabinetry, coordinated with the island's height, water exposure and the chosen accessory.

Other project-specific points

Project-specific, with no reference height. Each appears on a project only when it is selected, and none is priced or included automatically.

  • GEN-P1 Doorbell push-button or video doorbell / intercom entrance stationThe door and its frame, the entrance wall and the cable route to the indoor unit.
  • GEN-P2 Private distribution boardService access to the board, the meter position and the wall or cabinet it sits in.
  • GEN-P3 Wired Wi-Fi access pointThe ceiling or wall position and the data cable route to it.
  • GEN-P4 CCTV recorderVentilation around the recorder and the cable routes to the cameras and the network.
  • GEN-P5 DimmerThe lamp and driver it controls, and the switch position.

Four rooms, five checks

Kitchen, bedroom, living room and bathroom each get the same five checks, with the points grouped by everyday use. Optional equipment appears only when you select it, and nothing here is an automatic inclusion. A height beside an item is its point's starting coordination datum, in millimetres; an item with no height is project-specific.

  1. Position Dimension the point horizontally on the plan and vertically from finished floor level.
  2. Fit Check the actual furniture, accessory plate, appliance and cabinet dimensions.
  3. Use Confirm reach, switching, glare, trailing cables and simultaneous appliance use.
  4. Service Show how connections, drivers and equipment can be isolated, accessed and replaced.
  5. Verification Distinguish proposed design positions from contractor-verified electrical arrangements.

Kitchen

Coordinate with: Actual appliances, worktop height, backsplash, sink and plumbing, cabinet modules, ventilation and service access.

Appliances, simultaneous use and cabinet services are coordinated together.

Position
Dimension each point on the plan and from FFL against the actual worktop height and backsplash joints; the island's point is set per island.
Fit
Check the actual appliance, worktop, backsplash, sink and cabinet-module dimensions, so that no plate or connection sits behind fixed furniture or under equipment.
Use
Confirm reach at the worktop, which appliances run together, and where cables would trail across the work zone.
Service
Show how each appliance, driver and cooling connection is isolated, reached and replaced without removing fixed cabinetry; keep ventilation and service access clear.
Verification
Mark each point Proposed until the appointed electrical installation contractor has verified the arrangement. Appliance connections follow the selected model's installation instructions.

Cooking

  • KIT-09 1400 mm
  • KIT-05 600 mm · KIT-06 1400 mm
  • KIT-07 1400 mm
  • KIT-10 2200 mm

Cold, wet and cleaning

  • KIT-03 1200 mm
  • KIT-04 600 mm
  • Project-specific: to be coordinated
  • Project-specific: to be coordinated
  • Project-specific: to be coordinated

Worktop and island

  • KIT-01 1150 mm
  • KIT-02 no fixed height, set per island
  • KIT-08 1400 mm
  • Project-specific: to be coordinated
  • Project-specific: to be coordinated
  • Project-specific: to be coordinated

Light and air

  • Project-specific: to be coordinated
  • Project-specific: to be coordinated

Bedroom

Coordinate with: Bed and mattress height, bedside furniture, wardrobe doors, mirrors, curtain pockets, airflow and sleeping positions.

Both sides of the bed are covered, and so is switching from the entry and from the bed.

Position
Dimension both bedsides, the entry and bedside switching, and each light on the plan and from FFL, against the bed and mattress height.
Fit
Check the bed, mattress, bedside furniture, wardrobe doors, mirrors and curtain pockets, so that no plate or switch is covered or struck by a door.
Use
Confirm reach from each side of the bed, switching from the entry and from the bed, glare at the sleeping positions and trailing charging cables.
Service
Show how drivers, air-conditioning and fan isolation and any curtain motor are reached and replaced, with airflow kept clear.
Verification
Mark each point Proposed until the appointed electrical installation contractor has verified the arrangement. Air-conditioning, fan and curtain-motor arrangements are the contractor's to verify.

Beside the bed

  • BED-01 700 mm
  • BED-01 700 mm

Light

  • GEN-06 1400 mm
  • GEN-06 1400 mm
  • Project-specific: to be coordinated
  • Project-specific: to be coordinated

Dressing and desk

  • Project-specific: to be coordinated
  • GEN-02 1100 mm · LIV-02 950 mm

Air and curtains

  • GEN-03 2200 mm
  • Project-specific: to be coordinated
  • Project-specific: to be coordinated

Living room

Coordinate with: Final furniture layout, TV bracket and screen, console, cable routes, ceiling details, glare and maintenance access.

TV, seating, media and data, and layered lighting are coordinated together.

Position
Dimension the TV, media and data points, seating-area charging, lamp sockets and each lighting layer on the plan and from FFL, against the final furniture layout.
Fit
Check the TV bracket and screen, console, seating, cable routes and ceiling details, so that no plate or connection is hidden behind fixed furniture.
Use
Confirm reach from the seating, glare on the screen, trailing cables across walkways, and which media and work equipment run together.
Service
Show how the router, media equipment, drivers and air-conditioning isolation are reached and replaced, and how lamps and fittings are maintained.
Verification
Mark each point Proposed until the appointed electrical installation contractor has verified the arrangement. Network, media and lighting arrangements are verified alongside the power.

Screen and media

  • LIV-01 350 mm · LIV-02 950 mm
  • LIV-03 1100 mm

Seating and work

  • Project-specific: to be coordinated
  • GEN-01 350 mm
  • GEN-02 1100 mm

Light

  • Project-specific: to be coordinated

Air and curtains

  • GEN-03 2200 mm
  • Project-specific: to be coordinated
  • Project-specific: to be coordinated

Bathroom

Coordinate with: Wet-area restrictions, basin and shower positions, mirror cabinet, ceiling, plumbing, equipment instructions and access.

Wet-area review before any point is confirmed. No height on this sheet implies permission to install an accessory there.

Position
Do the wet-area review first. Only then dimension any point on the plan and from FFL; a height never implies a point may go there.
Fit
Check the basin and shower positions, mirror cabinet, ceiling, plumbing and the equipment's own dimensions and instructions.
Use
Confirm reach and switching, and what is used together, such as the mirror light, a demister and the exhaust fan.
Service
Show how the water heater, exhaust fan and mirror equipment can be isolated, reached and replaced.
Verification
Wet-area suitability, equipment selection and electrical protection need the appointed electrical contractor’s verification before any point is confirmed.

At the mirror

  • BAT-01 1200 mm
  • Project-specific: to be coordinated
  • BAT-02 1200 mm

Water and air

  • BAT-03 1400 mm · BAT-04 1400 mm
  • Project-specific: to be coordinated
  • Project-specific: to be coordinated

Light

  • Project-specific: to be coordinated

Connection schedule, a specimen

Height answers only one part of electrical planning. A connection schedule records, for each appliance or point, what it needs and who verifies it. These three lines are illustrations: they describe no project and no product, and ELS calculates no cable size, protection or circuit rating.

KIT-05

Point ID
KIT-05
Room
Kitchen
Appliance and model status
Under-counter oven; model not chosen yet
Rated load
From the selected product's documentation
Connection requirement
Per the manufacturer's instructions; the contractor confirms the arrangement
Plan position
Wall and offset dimensioned on the plan
Final height, FFL to CL
Set per project; the reference datum is 600 mm
Isolation and access
Adjacent service bay, reachable without removing the oven
Cabinet, plumbing and lighting interfaces
Cabinet cut-out and ventilation
Trade
Appointed electrical installation contractor
Verification status
Proposed

KIT-02

Point ID
KIT-02
Room
Kitchen
Appliance and model status
Island socket; accessory not chosen yet
Rated load
From the selected product's documentation
Connection requirement
Per the manufacturer's instructions; the contractor confirms the arrangement
Plan position
Wall and offset dimensioned on the plan
Final height, FFL to CL
Set per island, below the worktop on a side or end panel
Isolation and access
Reachable without moving fixed furniture
Cabinet, plumbing and lighting interfaces
Island panel, floor or cabinet routing, water exposure
Trade
Appointed electrical installation contractor
Verification status
Proposed

BAT-03

Point ID
BAT-03
Room
Bathroom
Appliance and model status
Water heater; model not chosen yet
Rated load
From the selected product's documentation
Connection requirement
Per the manufacturer's instructions; the contractor confirms the arrangement
Plan position
Wall and offset dimensioned on the plan
Final height, FFL to CL
Set after the wet-area review; the reference datum is 1400 mm
Isolation and access
Isolation outside the wet area where the contractor requires it
Cabinet, plumbing and lighting interfaces
Plumbing and the ceiling or wall
Trade
Appointed electrical installation contractor
Verification status
Proposed

Appliance load schedule

Tell us which appliances you use together, so their power requirements and positions can be coordinated before work starts.

This page stays focused on where each point goes. The load schedule records what each point must serve, and is linked to it by point ID. It uses your own equipment list, where you type the model and the quantity.

  1. Manufacturer-rated current takes precedence over an estimate.
  2. An unknown value stays unknown. It is never shown as zero.
  3. Rated input power only: cooling capacity and cooking output are not electrical input.
  4. The voltage is the appliance's rated voltage, or unknown. ELS assumes none.
  5. Estimated current is input watts ÷ voltage, for a single-phase load, assuming power factor 1. Motors, compressors and electronic equipment can need more information from the manufacturer.
  6. A sum of currents is a connected-load estimate. It is not the home's maximum demand.
  7. Appliance current, plug or fuse rating and circuit-breaker rating are different things. ELS sizes no cable, breaker, protection or circuit, and a low estimate does not show that a socket is suitable.
  8. For lighting, record the driver's electrical input and the load it supports, and where the driver can be reached to replace it. Low-voltage LED output current is not mains input current.
  9. Your inputs and the contractor's verification are kept apart. This page cannot mark anything contractor verified.

What to capture in each room

Kitchen
Hob, oven, microwave, kettle, coffee machine, dishwasher, fridge, hood, purifier, an optional disposer and countertop appliances.
Bedroom
Air-conditioning, fan, dressing appliances such as a hair dryer, desk equipment, TV, lighting and powered curtains.
Living room
Air-conditioning, fan, TV and media, computer or work corner, lighting, charging, and powered furniture or curtains.
Bathroom
Instant or storage water heater, ventilation, mirror demister, permitted grooming equipment and an optional powered toilet.

Specimen lines

KIT-C09 ← KIT-08

Point ID
KIT-C09
Appliance
Illustration only: a hypothetical appliance
Model and quantity
No model; quantity 1
Input power
2,300 W
Voltage
230 V
Phase
Single phase
Rated current
unknown
Estimated current
10.0 A (2,300 W ÷ 230 V; single phase, power factor 1 assumed)
Source or reference
The paper's own illustration, not a product
Connection requirement
Per the manufacturer's instructions; the contractor confirms
Simultaneous-use group
A
Verification status
Proposed

KIT-C03 ← KIT-03

Point ID
KIT-C03
Appliance
Fridge; model not chosen yet
Model and quantity
No model; quantity 1
Input power
unknown
Voltage
unknown
Phase
unknown
Rated current
unknown
Estimated current
unknown
Source or reference
From the selected product's nameplate or manual
Connection requirement
Per the manufacturer's instructions; the contractor confirms
Simultaneous-use group
B
Verification status
Proposed

Connected-load estimate (specimen): 10.0 A at 230 V (1 row). The second line has no current and no voltage, so it is not added and is not counted as zero.

Appliance & Equipment Coordination

Your appliance load schedule

Kept on this device, with your equipment list. Nothing is sent to ELS, ALUMAX or anyone else; you copy, print or download what you choose to send. Your inputs are yours: this page cannot mark anything verified by an electrical contractor.

How to use it

  • An ELS design standard, not a statutory height. This sheet provides ELS planning references. Final locations and electrical arrangements must meet applicable Sarawak requirements and the selected equipment’s installation instructions, verified by the appointed electrical installation contractor.
  • The appliance manual wins. Check dishwasher, oven, fridge, AC, water heater and cooker connection positions at design freeze.
  • Wet zones win. Bathroom points go only where the wet-zone requirements permit.
  • Plan position is drawn, height is this sheet. Mark the wall and offset on the M&E plan; the height comes from the schedule.
  • Wiring is done by a registered electrical contractor.

Not on this sheet?

A point this schedule does not list (for example an EV charger) is set per project and drawn on the M&E plan until ELS adds a datum for it.

Measured FFL → CL

Every height is measured from finished floor level (FFL) to the centre line (CL) of the accessory — not the underside of the box, not the top of the plate. Set FFL from the finished floor build-up, not the slab.

The floor box is the one exception: it sits flush with FFL, and its position is dimensioned on the plan.

Download the sheet

The PDF and CSV are issued in English only.

Power, data & security