ELS Design Standard · Residential

Electrical Datum

One datum per point. No site guessing.

v1.0 · 6 Oct 2026

Measured FFL → CL

Every height is measured from finished floor level (FFL) to the centre line (CL) of the accessory — not the underside of the box, not the top of the plate. Set FFL from the finished floor build-up, not the slab.

The floor box is the one exception: it sits flush with FFL, and its position is dimensioned on the plan.

The nine numbers

Every point on the schedule except the floor box takes one of these nine heights, in millimetres.

  1. 350General
  2. 600Low appliance / outdoor
  3. 700Bedside
  4. 950TV
  5. 1100Desk / island
  6. 1150Kitchen worktop
  7. 1200Service / fridge / vanity
  8. 1400Controls / isolators
  9. 2200Hood / AC / high-level equipment
030060090012001500180021002400Desk 750Worktop 900Wall cabinet 1500350General600Low appliance / outdoor700Bedside950TV1100Desk / island1150Kitchen worktop1200Service / fridge / vanity1400Controls / isolators2200Hood / AC / high-level equipmentFFL 0
Wall elevation drawn to scale, 0 to 2,400 mm. Each square is one 86 × 86 mm plate. Dashed lines are references, not datums.

The schedule by use

Heights in millimetres, FFL → CL.

General living 6
PointDatum height (mm)Placement rule
General 13A socket350Dry-area universal socket
Bedside socket / USB700Above typical bedside cabinet
TV console socket350Low equipment zone
Wall-TV power + data950Concealed behind TV
Desk / study socket1100Above typical 750 mm desk
Router / network equipment power1100Prefer dedicated structured-media location
Kitchen 10
PointDatum height (mm)Placement rule
Kitchen countertop socket1150Typical 900 mm worktop
Kitchen island socket1100Side/end panel, not worktop surface
Refrigerator dedicated socket1200Adjacent accessible service zone, not trapped behind fridge
Dishwasher socket600In adjacent cabinet/service bay, never directly behind dishwasher
Under-counter oven connection / socket600Adjacent cabinet/service bay
Built-in oven isolator1400Accessible outside appliance cavity
Built-in microwave socket1400Adjacent service cabinet
Coffee-machine / appliance tower socket1400Accessible within adjacent appliance/service zone
Cooker / induction hob isolator1400Dedicated circuit; not directly above hob
Cooker hood socket2200Concealed/accessibly located above or within hood cabinet
Laundry 2
PointDatum height (mm)Placement rule
Washing-machine socket1200Beside machine, away from hoses
Dryer socket1200Dedicated accessible point
Bathroom 4
PointDatum height (mm)Placement rule
Mirror / mirror-cabinet power1200Coordinate basin/mirror geometry
Bathroom shaver socket1200Only where wet-zone requirements permit
Instant water-heater isolator1400Outside inappropriate wet zone
Storage water-heater isolator1400Accessible outside wet zone
Mechanical 3
PointDatum height (mm)Placement rule
Air-conditioner isolator2200Near equipment, accessible for servicing
15A dedicated AC/equipment outlet2200Where equipment/system specifically requires 15A
Water-pump isolator1200Accessible, dry/serviceable location
External 4
PointDatum height (mm)Placement rule
Outdoor general socket600Weatherproof and above normal splash zone
Balcony socket600Weatherproof
Autogate power / isolator1200Protected service location
CCTV / security equipment power2200High-level service point where appropriate
Special 1
PointDatum height (mm)Placement rule
Floor box0 · flush with FFLFlush with finished floor; location dimensioned in plan
Controls 2
PointDatum height (mm)Placement rule
Light switch1400ELS control datum
General appliance isolator1400ELS common control datum

How to use it

  • An ELS design standard, not a statutory height. These are the heights ELS draws and coordinates to. No regulation sets them.
  • The appliance manual wins. Check dishwasher, oven, fridge, AC, water heater and cooker connection positions at design freeze.
  • Wet zones win. Bathroom points go only where the wet-zone requirements permit.
  • Plan position is drawn, height is this sheet. Mark the wall and offset on the M&E plan; the height comes from the schedule.
  • Wiring is done by a registered electrical contractor.

Not on this sheet?

A point this schedule does not list (for example an under-sink water purifier or an EV charger) is set per project and drawn on the M&E plan until ELS adds a datum for it.